HMCP007C0C
Motor Circuit Protection (MCP)


Eaton HMCP007C0C Motor Circuit Protection (MCP)
Series-C
MCP
Part Index
CLICK HERE

HMCP (3-Pole) Shown

HMCP007C0C Motor Circuit Protection (MCP)

F-Frame — 600 Vac Maximum, 250 Vdc Maximum
NEMA
Starter
Size
Continuous
Amps
Cam
Setting
Motor
Full Load
Current
Amperes
(FLA)(1)
MCP
Trip
Setting(2)
0 7 A 1.5–2.0 21
B 2.1–2.5 28
C 2.6–3.1 35
D 3.2–3.6 42
E 3.7–3.9 49
F 4.3–4.7 56
G 4.8–5.2 63
H 5.3–5.7 70

NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.

(2) For DC applications, actual trip levels are approximately 40% higher than values shown.

All GMCP 3–63A come with line and load steel body terminals for Cu only wire.

UL recognized and CSA approved