Menu


Moeller Z5-100/FF250
is now
EATON XTOB100LC1

For Separate Din Rail Mounting. Use with ANY Contactor

SAME EXACT PART- ONLY PART # CHANGE
Part Adjustable
Setting Range
Normally Open Normally Closed Short Circuit Protection
by fuses
max. 600 V
AC
by Circuit
Breaker max.
600 V AC
Z5-100/FF250 70 - 100 1 1 225 225

Z5-70/FF250


(actual part may vary)

Z5 Series Overloads

Adjustable
Range
Short Circuit Protection
(Max 600 VAC)
Moeller Logo Eaton Logo
Fuses (Amps) Circuit Breaker
(Amps)
50 - 70 125 125 Z5-70/FF250 (1) XTOB070LC1 (1)
70 - 100 225 225 Z5-100/FF250 (1) XTOB100LC1 (1)
95 - 125 250 250 Z5-125/FF250 (1) XTOB125LC1 (1)
120 - 160 600
Cass J
400 Z5-160/FF250 (1) XTOB160LC1 (1)
160 - 220 500
Class J
500 Z5-220/FF250 (1) XTOB220LC1 (1)
200 - 250 400
Class J
600 Z5-250/FF250 (1) XTOB250LC1 (1)

(1) Overload has one normally closed contact that opens upon trip and one normally open contact that closes when tripped.

Class 10A overload, Trip response from 2 to 10 seconds, Ambient compensated, Bi-Metallic tripping mechanism, Phase failure sensitive to IEC/EN 60947, Manual/Automatic reset button, Built in NO and NC auxiliary contacts.

Z5 Overloads
Mount Directly on these Contactors

Amps HP@ Built-in Contactor Auxiliary Moeller Logo Eaton Logo
AC-3 AC-1 240 480
185 337 60 125 2 N.O. DILM185/22 XTCE185L22
2 N.C. -- --
225 386 75 150 2 N.O. DILM225/22 XTCE225L22
2 N.C. -- --
250 429 100 200 2 N.O. DILM250/22 XTCE250L22
2 N.C. -- --

Z5 Overloads
Created: 1/30/2014
[303 KB]pdf icon

Mechanical Push Rod for Z5-100/FF250


Click to View Accessory Options

Z5-100/FF250 Typical Wiring

ZB32 overload wirediagram

Z5-100/FF250 Dimensions


ZB32-10 Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches
 