RE-PKZ2 and RS-PKZ2
Remote Control Drives

Remote control drives can be used with both the motor protector and motor protector combination. They are used to electrically operate the motor protector. They can be switched off at the device and thumb-grip handle can be padlocked using a 6 mm padlock. Suitable for use with either AC or DC voltages. Can be combined with undervoltage trips and shunt trips.

Always used standard auxiliary contact Type NHI when using remote control drives to electrically signal the open or closed status of the motor protector. Remote control drives cannot be used in conjunctions with the (R)H-PKZ2 door interlock handle. Mounting is possible in both ON and OFF positions of the motor protector. An internal electronic interlock always sets OFF as the default setting.

The thumb grip handle has 2 positions: HAND and AUTO. In HAND: the drive displays the color GREEN and blocks any remote electrical actuation. The internal signaling contact 33/34 is open. In AUTO: the drive displays the color RED, indicating that remote electrical actuation is possible. The internal signaling contact 33/34 is closed.


As indicated by the red arrow and green coloring. PKZ2 unit sold seperately.

RE-PKZ2
(110-120V50/60HZ,DC)

Used to electrically operate the PKZ2. Line voltage control.

OFF and RESET separate.

Line and control feeds have the same potential.  The control section can be energized by a single impulse of 15 ms duration, or by a maintained contact.  Upon energizing, the line connection draws its power requirement (700 VA/W for a duration ms 30 ms) directly from the line.

Control section can also be actuated via auxiliary contacts from various Moeller Electric components: NHI, AGM, ETR4-VS3, EK... and dry output contacts from PLCs with no RC filter type surge suppression.

RE-PKZ2 (24V50/60HZ,DC)

Used to electrically  operate the PKZ2. Control voltage from external source such as a PLC.

OFF equals RESET.

RS-PKZ2
(110-120V50/60HZ,DC)

Used to electrically  operate the PKZ2.

Line control sections are galvanically separated.  The control section is energized solely from a 24V DC source by a single impulse or by a maintained contact.  Suitable for energizing directly from an electronic PLC output.

Upon energizing, the line connection draws its power requirement (700 VA/W for a duration for 30 ms) directly from the line.

RS-PKZ2 (24V50/60HZ,DDC)

Used to electrically  operate the PKZ2.