Motor data
Rated short-circuit current
Setting
Range
Overload
Release
Ir
Old Moeller
Part Number
New Eaton
Part Number
380 – 415 V
Coordination
type “1”
lq
kA
380 – 415 V
Coordination
type “2”
lq
kA
100 3.0 - 12.0A MSC-DEA-12-M7(24VDC) XTSEA012B007BTDNL

MSC-DEA-12-M7(24VDC) Technical Data

Delivery programme
Basic function DOL starters (complete devices)
Basic device MSC
 
Notes Also suitable for motors with efficiency class IE3.
IE3-ready devices are identified by the logo on their packaging.
Motor rating
Motor Rating — AC-3
380 V 400 V 415 V P kW 3
Rated operational current — AC-3
400 V Ie A 6.6
Rated short-circuit current 380 - 400 V Iq kA 100
Setting range
Setting range of overload releases    Ir A 3 - 12
Short-circuit releases     
Non-delayed    Irm A 168
Coordination     Type of coordination "1"
Contact sequence
Actuating voltage 24 V DC
Motor-protective circuit-breakers PKE12/XTU-12
Contactor DILM7-10(...)
DOL starter wiring set
Mechanical connection element and electrical electric contact module PKZM0-XDM12

Notes
The DOL starter (complete devices) consists of a PKE motor-protective circuit-breaker and a DILM contactor.

With the adapter-less top-hat rail mounting of starters up to 15A, only the motor-protective circuit-breaker on the top-hat rail requires an adapter.

The contactors are provided with mechanical support via a mechanical connection element.

Control wire guide with max. 6 conductors up to 2.5°mm external diameter or 4 conductors up to 3.5°mm external diameter.

From 16 A, the motor-protective circuit-breaker and contactor are mounted on the top-hat rail adapter plate.

The connection of the main circuit between PKE and contactor is established with electrical contact modules.

When using DILA-XHIT... auxiliary contacts with MSC-DE-... DOL starters, the plug-in electrical connectors can be removed without removing the front-mounted auxiliary contact.

Cannot be combined with NHI-E...PKZ0-C.

MSC-DEA... DOL starters are prepared for communications via SmartWire-DT. In order to be used this way, they first need to be expanded with the PKE-SWD-32 communications module.

Motor output/rated motor current
Motor Rating
P
kW
Rated Motor Current AC-3
220 V
230 V
240 V

Iq=100kA
I
A
380 V
400 V

Iq=100kA
I
A
415 V

Iq=50kA
I
A
0.75 3.2 - -
1.1 4.6 - -
1.5 6.3 3.6 3.6
2.2 - 5 5
3 - 6.6 6.6
Technical data
General
Standards IEC/EN 60947-4-1, VDE 0660
Main conducting paths
Rated impulse withstand voltage Uimp V AC 6000
Overvoltage category/pollution degree     III/3
Rated operational voltage Ue V 230 - 415
Rated operational current
Open, 3-pole: 50-60 Hz
380 V 400 V
Ie A 7
Additional technical data
Motor protective
circuit breaker PKZM0, PKE
PKZM0 motor-protective circuit-breakers,
see motor-protective
circuit-breakers/PKZM0 product group
DILM contactors,
see contactors product group
DILET timing relay, ETR,
see contactors, electronic
timing relays product group
DC Operated Sealing W 3
Data for design verification according to IEC/EN 61439
Technical data for design verification
Heat dissipation capacity Pdiss W 0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal
stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance
of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance
of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance
to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear
needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear
needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear
needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear
needs to be evaluated.
10.6 Incorporation of switching devices
and components
Does not apply, since the entire switchgear
needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made
of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible
for the temperature rise calculation.
 Eaton will provide heat dissipation data
for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
The specifications for the switchgear
must be observed.
10.13 Mechanical function The device meets the requirements,
provided the information in
the instruction leaflet (IL) is observed.
Technical data ETIM 5.0
Low-voltage industrial components (EG000017) / Motor starter combination (EC001037)
Electric engineering, automation, process control engineering / Low-voltage switch technology /
Load breakout, motor breakout / Motor starter combination (ecl@ss8-27-37-09-05 [AJZ718009])
Function Direct starter
Rated control supply voltage Us at AC 50HZ V 0 - 0
Rated control supply voltage Us at AC 60HZ V 0 - 0
Rated control supply voltage Us at DC V 24 - 24
Voltage type for actuating DC
Rated operation power at AC-3, 400 V kW 3
Rated operation current Ie A 6.6
Conditioned rated short-circuit current Iq kA 100
Setting range overload protector A 3 - 12
With short-circuit release Yes
Type of coordination 2
Connection type main current circuit Screw connection
Degree of protection (IP) IP20
Suited for bus connection Yes

MSC-DEA-12-M7(24VDC) Dimensions

MSC-DEA-12-M7(24VDC) Dimensions

Inch to MM Conversion

Convert to MM

MM to Inch Conversion

Convert to Inches