| Typical Full-Load Motor Current Chart for Three Phase Alternating-Current Motors | |||
|
|||
| HP | 208 Volts | 230 Volts | 460 Volts |
| 1/2 | 2.4 | 2.2 | 1.1 |
| 3/4 | 3.5 | 3.2 | 1.6 |
| 1 | 4.6 | 4.2 | 2.1 |
| 1 1/2 | 6.6 | 6.0 | 3.0 |
| 2 | 7.5 | 6.8 | 3.4 |
| 3 | 10.6 | 9.6 | 4.8 |
| 5 | 16.7 | 15.2 | 7.6 |
| 7 1/2 | 24.2 | 22 | 11 |
| 10 | 30.8 | 28 | 14 |
| 15 | 46.2 | 42 | 21 |
| 20 | 59.4 | 54 | 27 |
| 25 | 74.8 | 68 | 34 |
| 30 | 88 | 80 | 40 |
| 40 | 114 | 104 | 52 |
| 50 | 143 | 130 | 65 |
| 60 | 169 | 154 | 77 |
| 75 | 211 | 192 | 96 |
| 100 | 273 | 248 | 124 |
| 125 | 343 | 312 | 156 |
| 150 | 396 | 360 | 180 |
| 200 | 528 | 480 | 240 |
| 250 | -- | -- | 302 |
| 300 | -- | -- | 361 |
| 350 | -- | -- | 414 |
| 400 | -- | -- | 477 |
| 450 | -- | -- | 515 |
| 500 | -- | -- | 590 |
| For 90 and 80 percent power factor, the above figures shall be multiplied by 1.1 and 1.25 respectively. | |||